Tools RTD Pt100 / Pt1000 Calculator

RTD Pt100 / Pt1000 Calculator

Convert RTD resistance to temperature and back for Pt100 and Pt1000 sensors, using the IEC 60751 Callendar-Van Dusen equation. °C, °F, and out-of-range fault checks. Free.

Pt100 resistance reference (IEC 60751, α = 0.00385)

A Pt100 reads exactly 100 Ω at 0 °C and rises about 0.385 Ω per °C. Pt1000 is the same curve scaled ×10 (1000 Ω at 0 °C, ~3.85 Ω/°C), which makes lead-wire resistance a smaller share of the reading.

Temp (°C) Pt100 (Ω) Pt1000 (Ω)
−200 18.52 185.2
−100 60.26 602.6
0 100.00 1000.0
25 109.73 1097.3
50 119.40 1194.0
100 138.51 1385.1
200 175.86 1758.6
400 247.09 2470.9
600 313.71 3137.1
850 390.48 3904.8

Reading looks wrong?

An open RTD element or a broken lead reads as a very high resistance (off the top of the scale); a shorted sensor or lead reads near 0 Ω. A reading that's plausible but off by a fixed amount is usually lead-wire resistance on a 2-wire hookup — switch to a 3- or 4-wire connection to cancel it. For the trade-offs between RTDs and thermocouples and how to wire each, see RTD vs thermocouple: which to use.